MIME-Version: 1.0 Content-Type: multipart/related; boundary="----=_NextPart_01CCCD50.F5FF0370" This document is a Single File Web Page, also known as a Web Archive file. If you are seeing this message, your browser or editor doesn't support Web Archive files. Please download a browser that supports Web Archive, such as Windows® Internet Explorer®. ------=_NextPart_01CCCD50.F5FF0370 Content-Location: file:///C:/6465E2A5/PS6000rmi-1-a_no_header_brochure.htm Content-Transfer-Encoding: quoted-printable Content-Type: text/html; charset="us-ascii"


PS6=
000rmi-1-A Series UPS 3U X 38cm =
deep
Fully Ruggedized stainless steel chassis MIL-STD-901D-A MIL-STD-167 Shipboa=
rd.
Test results available. This unit is housed in a 304grade stainless
chassis. It has a front mount=
ed
High G Input circuit breaker with finger guard. A front mounted bypass =
(as s=
hown)
is an option which switches the input directly to the output- bypassing the=
UPS
altogether. Also this unit has
conformal coating applied to the electronics. An Input Isolation transforme=
r is
available and can be mounted to the rear of the unit. 1000s in use as 120V
model with the US Navy. This =
unit
is now available as a 230V model.
Out=
put
> Output Power Capacity 1000 Watts/ 1500VA
> Nominal Output Voltage co= nfigurable for 220V, 230V, or 240V. (120V Model is also available; PS6000-1-A) = This unit has an Automatic Voltage Regulator (AVR) circuit to stabilize output voltage without using the Inverter- thus it is more efficient while on MAIN= S
> Efficiency at Full Load 9= 5%
> Full Sine wave waveform- = Output voltage distortion Less than 5% at full load
> Output Frequency (sync to mains) 47 - 53 Hz for 50 Hz nominal, 57 - 63 Hz for 60 Hz nominal
> Crest Factor up to 5: 1= p>
> > Line Interactive sty= le UPS switches to Inverter in 2-8ms (that is less than ¼ of a cycle)= p>
> This unit performs automatic bi-weekly tests on i= ts inverter and does a battery load test to find bad batteries before they fai= l on you
> Output Connections: 2 Mil= itary is standard (or you can specify up to 6 connectors of your choice)
Input
> 1 ea. Miltary spec. connector. Nominal Input Voltage 230v or 120V for US models. (Wired for Ship= board delta power with dual pole High shock rated Miltary Spec. input circuit breaker)
> Input Frequency 50/60 Hz +/- 3 Hz (auto sensing)
> Input voltage range for m= ain operations 162 - 286V (International model)
> Input voltage adjustable range for mains operation 151 - 302V
Batteries & Runtime
> Batteries replaceable through front panel while
online
> Battery Type VRLA Mainten= ance-free sealed Lead-Acid battery with suspended electrolyte: l= eakproof 3-5 year life expectancy.
> Optional Premium 8-10 year higher
temperature -20°+60°C discharge rated batteries available as PSRBC8=
h
> Typical recharge time 3 hour(s)
> Typical Backup Time @ Half Load 25.6 minutes (500W)
> Typical Backup Time at Fu= ll Load 7 minutes (1000W)
Ps6000RMi-1-A
Communications & Management
> Interface Port(s) DB-9 (R= S-232), USB
> Optional Ethernet SNMP reporting card for configuration and alarm reporting using Powerchute™ software. Windows XP and later versions will recognize this UPS when connected via USB and configure itself for UPS operation.
Optional Ethernet SNMP with Remote temperature and Hum= idity sensor for reporting and alarming environmental conditions to a remote monitor PC<= /p>
> Front Control panel has:
> LED status display with l= oad and battery bar-graphs and On Line: On Battery: Replace Battery : an= d Overload = span>Indicators
> Audible Alarm (BEEP) when on battery: distinctive low battery alarm: configurable delays
> Front mounted Military Sp= ec +120G input circuit breaker with approved finger guard
> Optional front mounted Master Bypass Switch. This switches bypasses entire UPS = for Maintenance or if the UPS has failed. Only the Input circuit breaker is lef= t in line with the load.
Surge Protection and Filtering
> Surge energy rating 480 Joules, Filtering: Full time multi-pole noise filtering: 0.3% IEEE surge let-through: zero clamping resp= onse time: meets UL 1449
Physical
> Maximum Height 130 mm
> Maximum Width 432.00 mm= p>
> Maximum depth 381 mm
> Rack Height 3U
> Net Weight 25 KG
> Shipping Weight 33 KG
> Shipping Height 255 mm
> Shipping Width 594.00 mm<= /p>
> Shipping Depth 603.00 mm<= /p>
Environmental
> Operating Environment 0&d=
eg;+40°C
with standard batteries; -15°C + 50°C with our Premium
battery upgrade
<=
![endif]>> Operating Relative Humidity 0 - 95%
> Operating Elevation 0-3000 meters
> Storage Temperature -15 -= 45 °C
> Storage Relative Humidity= 0 - 95%
> Storage Elevation 0-15000 meters
> Audible noise at 1 meter = from surface of unit 46 dBA
> Online Thermal Dissipation 171 BTU/hr
Rohs 7b exemption C-tick,CE,EN 50091-1,EN 50091-2,TUV,VDE
Powerstar Incorporated
Gaithersburg, MD
+1-301-948-0713
info@powersta= rinc.com = &nb= sp; = Jan 2012